XW-8053AC

XW-8053AC 8-channel AC switch acquisition moduleXW-80531 product introductionXW-8053AC 8-channel AC switch acquisition module can be used to collect (150V-240V) AC switch (mains) signal, mainly used for computer room monitoring, industrial control or othe

contact
  • Detail
  • Parameter

XW-8053AC 8-channel AC switch acquisition module

XW-8053
1 product introduction
XW-8053AC 8-channel AC switch acquisition module can be used to collect (150V-240V) AC switch (mains) signal, mainly used for computer room monitoring, industrial control or other distributed data collection. Report interface using RS485 communication bus and standard MODBUS-RTU communication protocol, can be easily integrated into third-party applications.
1.1 product appearance
 
1.2 terminal definition
Refer to the following table for the position of the terminal. See the following table for the definition of the interface position.
Silk screen
definition
AC_L1
AC switch input FireWire channel 1
AC_L2
AC switch input FireWire channel 2
AC_L3
AC switch input FireWire channel 3
AC_L4
AC switch input FireWire channel 4
AC_L5
AC switch input FireWire channel 5
AC_L6
AC switch input FireWire channel 6
AC_L7
AC switch input FireWire channel 7
AC_L8
AC switch input live line 8
NC
air
AC_N
AC switch input zero line channel
D +
485 communication signal + or A
D-
485 communication signal - or B.
VIN +
Power supply is positive
VIN-
Negative power supply
& Note
1 Make sure to distinguish the zero line and live line of AC current, and strictly follow the wiring requirements, otherwise it will damage the product and cause an accident.
2 220V AC power line and zero line distinction method
Test pen: finger hold pen card, contact with the tip of the test wire (finger can not touch the pen tip), neon tube light tip tip is exposed to the line of fire
1.3 indicator
Indicators are located on the front of the module, as described in the following table.
Silk screen
definition
status
description
POWER
Power Indicator
bright
Power supply is normal
RUN
Running lights
Blinking
normal work
TX
Send light
Blinking
Communication port is sending data
RX
Receive light
Blinking
Communication port is receiving data
1 ~ 8
Switch status indicator
bright
The corresponding channel of the switch signal is high
& Note
Note: The corresponding channel indicator light, said the corresponding channel AC 220V switch access:
      The corresponding channel indicator off, indicating that the corresponding channel without AC 220V switch access:
1.4 Technical Specifications
Working conditions
power input
Range: 9 ~ 30VDC
Power consumption
<1W
Ambient temperature
-10 ℃ ~ 50 ℃
environment humidity
10% ~ 90% RH, no condensation
EMC indicators
Static Protection
Contact discharge: ± 6KV; Air discharge: ± 8KV
EFT protection
± 2KV
external structure
Length × width × height
125 * 73 * 44 mm
Communication parameters
Interface Type
RS485, pluggable terminal
Data Format
N, 8,1
Resolution
12bit
Data baud rate
1200 ~ 19200bps, the default 9600bps
Input channel
8-way AC switch signal input
input resistance
10K ohms (internal integration)

Online message