直播夜月官方版-直播夜月免费版app下载-直播夜月永久免费版下载

Welcome Shenzhen City Xwleak technology co.!
Professional liquid leak solution

You may be searching:

  • XW-DC-02
  • XW-DC-02

XW-DC-02

XW-DC-02 controller is a leak liquid detection equipment has the advantages of simple operation、high performance to price ratio .It is through the internal dial switch select different response sensitivity, in order to adapt to the different detectio

contact
  • Detail
  • Parameter



XW-DC-02 controller is a leak liquid detection equipment has the advantages of simple operation、high performance to price ratio .It is through the internal dial switch select different response sensitivity, in order to adapt to the different detection environment and class. XW-DC-02 controller output the relay contact signal, which can integrate with a various monitoring system, then realization of the remote control.

 

Key features

Stable and reliable

XW-DC-02 controller by using hardware circuit design,imported components, which can guarantee the high sensitivity detection,and also can avoid false alarms caused by external factors.The controller provide 1 sets of leakage alarm relay, the product also has a unique anti surge protection function.

Adjustable

The XW-DC-02 controller has a 4 bit shift switch, the user can chooseaccording to the detection sensitivity of different environmental ratingrequirements (cable length of 1cm - 50cm).

Simple and beautiful

XW-DC-02 controller uses industry standard module,DIN guide, field wiring all the installation can be completed easily through the terminal, when the leakage occurs, the relay action, leakage indicator light, a buzzer alarm,each part can automatic reset the controller after troubleshooting, return to a normal state, without the need for manual operation.

 

Technical parameters

 

 Characteristics  Reaction time  ≤2S
 Detection distance  200m
 Environmental ratings  Storage temperature  -40 oC ~60 oC(0 oF ~140oF)
 Working temperature  -20oC ~50 oC(-4 oF ~122oF)
 Humidity  5%~95%(no condensation)
 Power requirements  XW-DC-02  12~24VDC 12~24VAC
 Relay  Characteristic  1 set,normally open or close
 Ratings  AC125V,0.5A,DC12V,1A

 

System description

Xiangwei unlocated leak detection system,contain by the controller、pinout、sensor cable and related spare parts.

Wiring procedures:

①pinout ——The red, black core wires are respectively access controller panel R, B, then access to the two core threaded structure sensing cable XW 1100.

②signal output ——External equipment by the relay unit normally open and public output

③Power Supply ——XW-DC-02 controller can be connected with DC12~24V, AC12-24V

④sensitivity —— Open the shell poking gear switch,1 gear to 4 gear to enhance reaction sensitivity

⑤install —— Pull rail release valve, take XW-DC-02 controller placed horizontally on the DIN 35mm Industrial Rail, then lock release valve




Online message

在線留言

  • *Name(Please fill your name)
  • *Telephone(Please fill your phone number)
  • Email
  • *Purchase intention(Please fillproduct quantity and product description)
  • *code
contact us:

[email protected]


TOP
Online Service